2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
486
List Manual, 09/2017, A5E33842890
Description:
Sets the fault threshold for monitoring the motor temperature for motor temperature models 1 and 3.
Fault F07011 is output after the fault threshold is exceeded.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0615 to p5391.
Dependency:
Refer to: r0034, p0612, p0615, r0632, p5390
Refer to: F07011, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
Description:
Displays the ambient temperature for motor temperature models 1 and 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
Dependency:
Refer to: r0034
Note:
For firmware version < 4.7 SP6: parameter p0613 is not visible for users (this is a Siemens internal parameter).
Description:
Displays the alarm threshold for monitoring the motor temperature for motor temperature models 1 and 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p5390.
Dependency:
Refer to: p5390
Refer to: F07011, A07012, A07014
Note:
For firmware version < 4.7 SP6: parameter p5390 is not visible for users (this is a Siemens internal parameter).
Description:
Sets the fault threshold for monitoring the motor temperature for motor temperature models 1 and 3.
Fault F07011 is output after the fault threshold is exceeded.
The parameter value is an image of p5391.
p5391[0...n]
Mot_temp_mod 1/3 fault threshold / F thresh
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8017
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
120.0 [°C]
r5397
Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8019
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
r5398[0...n]
Mot_temp_mod 3 alarm threshold image p5390 / A thr image p5390
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
MDS
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8019
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
r5399[0...n]
Mot_temp_mod 3 fault threshold image p5391 / F thr image p5391
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
MDS
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8019
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......