2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
568
List Manual, 09/2017, A5E33842890
Description:
Sets the time interval for carrying out the forced checking procedure and testing the Safety switch-off signal paths.
Within the parameterized time, STO must have been de-selected at least once. The monitoring time is reset each
time that STO is de-selected.
Dependency:
Refer to: A01699
Note:
STO: Safe Torque Off
Description:
Displays the time remaining before dynamization and testing of the safety switch-off signal paths (forced checking
procedure).
Dependency:
Refer to: A01699
Description:
Sets the time interval for monitoring the forced checking procedure and testing the Safety switch-off signal paths for
STO via terminals on the Power Module.
Within the parameterized time, STO must have been de-selected at least once.
Dependency:
Refer to: r9662
Refer to: A01678
Note:
STO: Safe Torque Off
Description:
Displays the remaining time for monitoring the forced checking procedure and testing the Safety switch-off signal
paths for STO via terminals on the Power Module.
After the monitoring time set in p9661 has expired, an appropriate alarm is output.
Dependency:
Refer to: p9661
Refer to: A01678
Note:
PM: Power Module
STO: Safe Torque Off
p9659
SI forced checking procedure timer / SI FCP Timer
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2810
Min Max
Factory
setting
0.00 [h]
9000.00 [h]
8.00 [h]
r9660
SI forced checking procedure remaining time / SI FCP remain
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [h]
- [h]
- [h]
p9661
SI forced checking procedure STO via PM terminals time / FCP_dyn STO PM-T t
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [h]
9000.00 [h]
8.00 [h]
r9662
SI forced checking procedure STO via PM terminals remaining time /
FCP_dyn STO PM-T t
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [h]
- [h]
- [h]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......