SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
511
2 Parameters
2.2 List of parameters
Dependency:
Refer to: p8685
Note:
Booting in the NMT state pre-operational corresponds to the CANopen standard
Description:
Sets and displays the CANopen NMT state.
Value:
0:
Initialization
4:
Stopped
5:
Operational
127:
Pre-operational
128:
Reset node
129:
Reset Communication
Note:
The value 0 (initialization) is only displayed and cannot be set.
Description:
Sets the monitoring time for the process data received via the CAN bus.
A value that is not a multiple integer of the CANopen sampling time is rounded-off.
If no process data is received within this time, then fault F08702 is output.
Dependency:
Refer to: F08702
Note:
Value = 0: Monitoring is deactivated.
p2048: CANopen sampling time
Description:
Sets the communication parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1400 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8685
CAN NMT states / NMT states
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 129
127
p8699
CAN: RPDO monitoring time / RPDO t_monit
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [ms]
65535000 [ms]
0 [ms]
p8700[0...1]
CAN Receive PDO 1 / Receive PDO 1
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204, 9206
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......