2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
42
List Manual, 09/2017, A5E33842890
Description:
Display and connector output for the speed setpoint after the setpoint filters.
Description:
Display and connector output for the speed actual value.
Frequency components from the slip compensation (for induction motors) are not included.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Calculated from f_set - f_slip (unsmoothed)
Dependency:
Refer to: r0021, r0022
Note:
The speed actual value r0063[0] – smoothed with p0045 – is additionally displayed in r0063[1]. r0063[1] can be used
as process variable for the appropriate smoothing time constant p0045.
The speed (r0063[2]) calculated from the output frequency and slip can only be compared with the speed actual
value (r0063[0]) in the steady-state.
For U/f control, the mechanical speed calculated from the output frequency and the slip is shown in r0063[2] even if
slip compensation is deactivated.
Description:
Displays the actual system deviation of the speed controller.
Description:
Displays the slip frequency for induction motors (ASM).
Description:
Display and connector output for the unsmoothed output frequency of the power unit.
Frequency components from the slip compensation (induction motor) are included.
r0062
CO: Speed setpoint after the filter / n_set after filter
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6020, 6030, 6031
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0063[0...2]
CO: Actual speed / Actual speed
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6020, 6799
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0064
CO: Speed controller system deviation / n_ctrl sys dev
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6040
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0065
Slip frequency / f_Slip
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
2_1
Unit selection:
p0505
Func. diagram:
6310, 6700, 6727,
6730, 6732
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r0066
CO: Output frequency / f_outp
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
2_1
Unit selection:
p0505
Func. diagram:
6300, 6700, 6730,
6731, 6799
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......