2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
150
List Manual, 09/2017, A5E33842890
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
p0778[0...1]
CU analog outputs characteristic value y1 / CU AO char y1
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9572
Min Max
Factory
setting
-20.000 [V]
20.000 [V]
0.000 [V]
p0779[0...1]
CU analog outputs characteristic value x2 / CU AO char x2
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9572
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p0780[0...1]
CU analog outputs characteristic value y2 / CU AO char y2
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9572
Min Max
Factory
setting
-20.000 [V]
20.000 [V]
20.000 [V]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......