2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
474
List Manual, 09/2017, A5E33842890
Notice:
For bit 06:
Setting the bit sets the velocity actual value (r0061) permanently to 0.
For bit 13:
Setting the bit sets the commutation angle permanently to the commutation angle offset (p0431).
Note:
For bit 09:
A setting of bit = 0 will trigger a fault for the relevant channel if the actual value is invalid.
A setting of bit = 1 will trigger an alarm for the relevant channel if the actual value is invalid.
Zu Bit 10, 11:
If both channels are activated, the actual value is generated from the mean value of both channels. If a channel fails
(actual value invalid), it is not included when the mean value is generated.
For bit 14:
The bit is only evaluated for encoder 1. Otherwise no effect.
Description:
Sets the input circuit for the analog sensor.
Value:
0:
Differential
1:
Single-ended A, B
2:
Single-ended A*, B*
3:
Single-ended A, B sensitive
Note:
p4671 = 0:
The two signals on a track are evaluated differentially.
p4671 = 1:
Only the non-inverted signal on a track is evaluated.
p4671 = 2:
Only the inverted signal on a track is evaluated.
p4671 = 3:
Only the non-inverted signal on a track (high resolution) is evaluated.
Description:
Sets the voltage when the connected sensor is at actual value zero.
At this voltage channel A supplies an actual value of zero.
Description:
Sets the output voltage range to be mapped for the connected analog sensor.
The voltage range is determined by the following parameters:
- p4672 (voltage at actual value 0)
- p4673 (voltage per encoder period)
Note:
The minimum actual value which can be mapped is equal to p4672 - p4673/2.
The maximum actual value which can be mapped is equal to p4672 + p4673/2.
p4671[0...n]
Analog sensor input / Ana_sens inp
Access level:
4
Calculated:
-
Data type:
Integer16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 3 0
p4672[0...n]
Analog sensor channel A voltage at actual value zero / Ana_sens A U at 0
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-10.0000 [V]
10.0000 [V]
0.0000 [V]
p4673[0...n]
Analog sensor channel A voltage per encoder period / Ana_sens A U/per
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-10.0000 [V]
10.0000 [V]
6.0000 [V]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......