SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
261
2 Parameters
2.2 List of parameters
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
2:
Analog setpoint
6:
Fieldbus
7:
Analog setpoint 2
20:
Analog se no main setpoint
22:
Analog se analog setpoint
26:
Analog se fieldbus
27:
Analog se analog setpoint 2
60:
Fi no main setpoint
62:
Fi analog setpoint
66:
Ffieldbus
67:
Fi analog setpoint 2
70:
Analog setpoint 2 + no main setpoint
72:
Analog setpoint 2 + analog setpoint
76:
Analog setpoint 2 + fieldbus
77:
Analog setpoint 2 + analog setpoint 2
Dependency:
When changing this parameter, the following settings are influenced:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1503, p1511
Notice:
When executing a specific macro, the corresponding programmed settings are made and become active.
Description:
Sets the signal source for toggling between speed and torque control.
0 signal: Closed-loop speed control
1 signal: Closed-loop torque control
Dependency:
The input connectors to enter the torque are provided using p1511, p1512 and p1513.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1300
Notice:
If the closed-loop torque control is not activated (p1300) and a change is made to closed-loop torque control (p1501),
OFF1 (p0840) does not have its own braking response but pulse suppression when standstill is detected (p1226,
p1227).
Note:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source to freeze the estimated moment of inertia.
0 signal:
Moment of inertia estimator active
1 signal:
Determined moment of inertia frozen.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1300
p1501[0...n]
BI: Change over between closed-loop speed/torque control / Changeov n/M_ctrl
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2520, 6020
Min Max
Factory
setting
- - 0
p1502[0...n]
BI: Freeze moment of inertia estimator / J_estim freeze
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......