2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
356
List Manual, 09/2017, A5E33842890
Description:
Sets the delay time for the message "Motor stalled" (BO: r2198.7).
Dependency:
Refer to: r2198
Note:
In the open-loop speed controlled operating range (see p1755, p1756), vector control stall monitoring depends on
threshold p1745.
At higher speeds, the difference between flux setpoint r0083 and flux actual value r0084 is monitored.
Description:
Sets the current limit for output load identification.
A missing output load is displayed using the "Output load not available" message (r2197.11 = 1).
This message is output with a delay time (p2180).
Dependency:
Refer to: p2180
Notice:
For synchronous motors the output current can be almost zero under no load conditions.
Note:
Missing output load is signaled in the following cases:
- the motor is not connected.
- a phase failure has occurred.
Description:
Sets the delay time for the message "output load not available" (r2197.11 = 1).
Dependency:
Refer to: p2179
Description:
Sets the response when evaluating the load monitoring.
Value:
0:
Load monitoring disabled
1:
A07920 for torque/speed too low
2:
A07921 for torque/speed too high
3:
A07922 for torque/speed out of tolerance
4:
F07923 for torque/speed too low
5:
F07924 for torque/speed too high
6:
F07925 for torque/speed out of tolerance
p2178[0...n]
Motor stalled delay time / Mot stall t_del
Access level:
3
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8012
Min Max
Factory
setting
0.000 [s]
10.000 [s]
0.010 [s]
p2179[0...n]
Output load identification current limit / Outp_ld iden I_lim
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2002
Dyn. index:
DDS, p0180
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
8022
Min Max
Factory
setting
0.00 [Arms]
1000.00 [Arms]
0.00 [Arms]
p2180[0...n]
Output load detection delay time / Out_load det t_del
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8022
Min Max
Factory
setting
0 [ms]
10000 [ms]
2000 [ms]
p2181[0...n]
Load monitoring response / Load monit resp
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8013
Min Max
Factory
setting
0 6 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......