2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
394
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source for the position actual value of the position controller.
Dependency:
Refer to: r2521
Description:
Sets the time constant for the position setpoint filter (PT1).
Note:
The effective Kv factor (position loop gain) is reduced with the filter. This allows a softer control behavior with
improved tolerance with respect to noise/disturbances.
Applications:
- reduces the precontrol dynamic response.
- jerk limiting.
Description:
Setting for activation and weighting of the speed precontrol value.
Value = 0 % --> The precontrol is deactivated.
Dependency:
Refer to: p2535, p2536, r2563
Note:
When the axis control loop is optimally set as well as a precisely determined equivalent time constant of the speed
control loop, the precontrol factor is 100%.
Description:
Sets the "fractional" dead time to emulate the timing behavior of the speed control loop.
The multiplier that has been set refers to the position controller sampling time.
VECTOR: dead time = p2535 * 8000
Dependency:
Refer to: p2536
p2532
CI: LR position actual value / s_act
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
3
Calculated:
-
Data type:
U32 / Integer32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4015, 4020, 4025
Min Max
Factory
setting
- - 2521[0]
p2533[0...n]
LR position setpoint filter time constant / s_set_filt T
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
4015
Min Max
Factory
setting
0.00 [ms]
1000.00 [ms]
0.00 [ms]
p2534[0...n]
LR speed precontrol factor / n_prectrl fact
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
4015, 4025
Min Max
Factory
setting
0.00 [%]
200.00 [%]
0.00 [%]
p2535[0...n]
LR speed precontrol balancing filter dead time / n_prectrFlt t_dead
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
4015
Min Max
Factory
setting
0.00 2.00 0.00
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......