2 Parameters
2.2 List of parameters
Description:
Display and connector output for the actual following error.
This value is the deviation between the position setpoint - after fine interpolation - and the position actual value.
Notice:
When speed precontrol is active (p2534 > 0 %), the following applies:
To calculate this value, the position setpoint is delayed by two position controller clock cycles.
When speed precontrol is inactive (p2534 = 0 %), the following applies:
To calculate this value, the position setpoint is delayed by two position controller clock cycles.
Description:
Displays the speed at the input of the precontrol channel.
Note:
This display parameter is used for diagnostics even when the precontrol is inactive (p2534 = 0%).
Description:
Sets the moment of inertia for the torque precontrol.
Dependency:
Refer to: p2534, r2564
Note:
When calculating the torque precontrol value (r2654), the time derivation of the speed precontrol value is multiplied
by 2 PI * p2567.
For reasons associated with the compatibility to earlier firmware versions, the factory setting for p2567 = 1 kgm^2/2
PI. This means that CO: r2564 remains as standard the derivation over time of the speed precontrol value and is
referred, as before, to a moment of inertia of 1 kgm^2/2 PI. For torque precontrol, the moment of inertia can now be
directly entered into p2567 (instead of subsequently evaluating the precontrol value.
Description:
Sets the signal source to activate the function "STOP cam".
BI: p2568 = 1 signal
--> The evaluation of the STOP cam minus (BI: p2569) and STOP cam plus (BI: p2570) is active.
r2565
CO: LR following error actual / Following err act
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4015
Min Max
Factory
setting
- [LU]
- [LU]
- [LU]
r2566
LR speed input precontrol / n inp prectrl
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
4015
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p2567[0...n]
LR torque precontrol moment of inertia / M_prectr M_inertia
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
25_1
Unit selection:
p0100
Func. diagram:
4015
Min Max
Factory
setting
0.000000 [kgm²]
100000.000000 [kgm²]
0.159155 [kgm²]
p2568
BI: EPOS STOP cam activation / STOP cam act
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3630
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......