2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
576
List Manual, 09/2017, A5E33842890
Description:
Status signal for safety-relevant motion monitoring functions integrated in the drive.
Notice:
For bit 07:
An internal event is displayed if a STOP A ... F is active.
The signal state behaves in an opposite way to the PROFIsafe Standard.
Note:
This parameter is only supplied with actual values if SI Motion functions are active. For Safety Integrated Basic
Functions (STO), the value is equal to zero.
Description:
Enters the Safety Integrated password.
Dependency:
Refer to: F01659
Note:
It is not possible to change Safety Integrated parameters until the Safety Integrated password has been entered.
Description:
Enters a new Safety Integrated password.
Dependency:
A change made to the Safety Integrated password must be acknowledged in the following parameter:
Refer to: p9763
Description:
Acknowledges the new Safety Integrated password.
Dependency:
Refer to: p9762
Note:
The new password entered into p9762 must be re-entered in order to acknowledge.
p9762 = p9763 = 0 is automatically set after the new Safety Integrated password has been successfully
acknowledged.
r9742.0...15
CO/BO: SI Motion drive-integrated status signals (processor 2) / SI Mtn int stat P2
Access level:
4
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2840, 2855
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
STO or safe pulse suppression active
Yes
No
-
01
SS1 active
Yes
No
-
04
SLS active
Yes
No
-
07
Internal event
No
Yes
-
09
Active SLS stage bit 0
Set
Not set
-
10
Active SLS stage bit 1
Set
Not set
-
12
SDI positive active
Yes
No
2824
13
SDI negative active
Yes
No
2824
15
SSM (speed below limit value)
Yes
No
2823
p9761
SI password input / SI password inp
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p9762
SI password new / SI password new
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p9763
SI password acknowledgment / SI ackn password
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......