2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
34
List Manual, 09/2017, A5E33842890
Description:
Display and connector output for the energy values at the output terminals of the power unit.
Index:
[0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency:
Refer to: p0043
Note:
The signal can be displayed as process variable (scaling: 1 = 1 Wh).
This is enabled in p0043.
The display is also reset with p0040 = 1.
If an enable is present in r0043 when the Control Unit powers up, then the value from r0039 is transferred into r0042.
As r0039 serves as a reference signal for r0042, due to format reasons, the process energy display can only process
values of r0039 up to 2147483 kWh. r0039 should also be reset using this value.
Description:
Sets the signal source to enable/reset the process energy display in r0042.
BI: p0043 = 1 signal:
The process energy display is enabled in r0042.
Dependency:
Refer to: r0042
Description:
Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
Description:
Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
r0042[0...2]
CO: Process energy display / Proc energy disp
Access level:
2
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Wh]
- [Wh]
- [Wh]
p0043
BI: Enable energy usage display / Enab energy usage
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0
p0045
Display values smoothing time constant / Disp_val T_smooth
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6714, 8012
Min Max
Factory
setting
0.00 [ms]
10000.00 [ms]
4.00 [ms]
r0046.0...31
CO/BO: Missing enable signal / Missing enable sig
Access level:
1
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2634
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
7954
01
OFF2 enable missing
Yes
No
-
02
OFF3 enable missing
Yes
No
-
03
Operation enable missing
Yes
No
-
04
Armature short-circuit / DC braking enable
missing
Yes
No
-
05
STOP2 enable missing
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......