2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
290
List Manual, 09/2017, A5E33842890
Index:
[0] = Changeover ramp motor model
[1] = Changeover ramp model tracking
[2] = Changeover ramp zero frequency induction motor without encoder
[3] = Changeover ramp actual speed SESM without encoder
[4] = Enable speed controller SESM without encoder
[5] = Changeover ramp motor model SESM without encoder
[6] = Changeover ramp motor model PMSM without encoder
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
ASM: induction motor
PMSM: permanent-magnet synchronous motor
SESM: separately excited synchronous motor
Description:
Displays the difference between the motor model flux angle and the transformation angle.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM): Rs, Lh, and offset compensation.
Permanent-magnet synchronous motor (PMSM): kT
Dependency:
In U/f characteristic operating mode only bit 7 is relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note:
ASM: Induction motor
PMSM: permanent-magnet synchronous motor
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is de-
activated and is instead taken into account in the motor model.
In order that the correction values of the Rs, Lh and kT adaptation (selected using Bit 0 ... Bit 2) are correctly
accepted when changing over the drive data set, a dedicated motor number must be entered into p0826 for each
different motor.
r1778
Motor model flux angle difference / MotMod ang diff
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2005
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [°]
- [°]
- [°]
p1780[0...n]
Motor model adaptation configuration / MotMod adapt conf
Access level:
3
Calculated:
p0340 = 1,3,4
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0111 1100 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Select motor model ASM Rs adaptation
Yes
No
-
02
Select motor model ASM Lh adaptation
Yes
No
-
03
Select motor model PMSM kT adaptation
Yes
No
-
04
Select motor model offset adaptation
Yes
No
-
05
Select ASM Rr adaptation (only with
encoder)
Yes
No
-
06
Select pole position identification PMSM
encoderless
Yes
No
-
07
Select T(valve) with Rs adaptation
Yes
No
-
10
Filter time combination current like current
ctrl integral time
Yes
No
-
12
Start PMSM sensorless with last angle
Yes
No
-
13
Fast pulsed pole position identification
Yes
No
-
14
Delay of the precontrol speed to the motor
model
Yes
No
-
15
RESM Q flux model linear active
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......