SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
267
2 Parameters
2.2 List of parameters
Description:
Sets the power limit when motoring.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500, p1531
Note:
The power limit is limited to 300% of the rated motor power.
Description:
Sets the regenerative power limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0206, p0500, p1530
Note:
The power limit is limited to 300% of the rated motor power.
For power units without energy recovery capability, the regenerative power limit is preset to 30 % of the power
r0206[0]. For a braking resistor connected to the DC link (p0219 > 0), the power limit when generating is
automatically adapted.
For power units with energy recovery, the parameter is limited to the negative value of r0206[2].
Description:
Displays the maximum torque/force generating current as a result if all current limits.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Displays the maximum limit for the torque-generating current component.
Index 0 indicates the signal limited by the Vdc controller.
Index:
[0] = Limited
[1] = Unlimited
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
p1530[0...n]
Power limit motoring / P_max mot
Access level:
2
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
14_5
Unit selection:
p0505
Func. diagram:
6640
Min Max
Factory
setting
0.00 [kW]
100000.00 [kW]
0.00 [kW]
p1531[0...n]
Power limit regenerative / P_max gen
Access level:
2
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
14_5
Unit selection:
p0505
Func. diagram:
6640
Min Max
Factory
setting
-100000.00 [kW]
-0.01 [kW]
-0.01 [kW]
r1533
Current limit torque-generating total / Iq_max total
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2002
Dyn. index:
-
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
6640
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
r1536[0...1]
Current limit maximum torque-generating current / Isq_max
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2002
Dyn. index:
-
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
6640, 6710
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......