SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
279
2 Parameters
2.2 List of parameters
Description:
Displays the integral component of the Isq current controller (torque/force-generating current, PI controller).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the actual output of the Isd current controller (flux-generating current, PI controller).
The value contains the proportional and integral components of the PI controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the integral component of the Isd current controller (flux-generating current, PI controller).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the limit value for the integral component of the Isd current controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Sets the scaling of the quadrature arm decoupling
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
r1719
Isq controller integral component / Isq_ctrl I_comp
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6714
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r1723
CO: Isd controller output / Isd_ctrl outp
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6714
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r1724
Isd controller integral component / Isd_ctrl I_comp
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6714
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r1725
Isd controller integral component limit / Isd_ctrl I_limit
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6714
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
p1726[0...n]
Quadrature arm decoupling scaling / Transv_decpl scal
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6714
Min Max
Factory
setting
0.0 [%]
200.0 [%]
75.0 [%]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......