SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
581
2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the Safety Integrated status on the drive (processor 1 + processor 2).
Note:
This status is formed from the AND operation of the relevant status of the two monitoring channels.
Description:
The parameter is used for diagnostics.
Note:
For bit 00 = 1:
At least one Safety parameter has been changed that will only take effect after a POWER ON.
For bit 01 = 1:
Safety functions (basic functions or extended functions) have been enabled and are active.
For bit 02 = 1:
A safety-relevant component has been replaced. Data save required (p0977 = 1 or p0971 = 1 or "copy RAM to
ROM").
For bit 03 = 1:
A safety-relevant component has been replaced. Acknowledge (p9702 = 29) and save (p0977 = 1 or p0971 = 1 or
"Copy RAM to ROM") required.
Description:
Displays the clock cycle time for the Safety Integrated Basic Functions on processor 1.
Note:
Information regarding the relationship between monitoring clock cycle and response times can be found in the
following references:
- SINAMICS G120 Function Manual Safety Integrated
- technical documentation for the particular product
r9773.0...31
CO/BO: SI status (processor 1 + processor 2) / SI status P1+P2
Access level:
2
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2804
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
STO selected in drive
Yes
No
2804
01
STO active in drive
Yes
No
2804
02
SS1 delay time active in the drive
Yes
No
2804
04
SBC requested
Yes
No
2804
05
SS1 selected in the drive (Basic Functions)
Yes
No
-
06
SS1 active in the drive (Basic Functions)
Yes
No
-
30
Test stop required for STO via PM terminals Yes
No
-
31
Test stop required for STO
Yes
No
2810
r9776
SI diagnostics / SI diag
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Safety parameter changed POWER ON
required
Yes
No
-
01
Safety functions enabled
Yes
No
-
02
Safety component replaced and data save
required
Yes
No
-
03
Safety component replaced and
acknowledge/save required
Yes
No
-
r9780
SI monitoring clock cycle (processor 1) / SI mon_clk cyc P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2802
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......