Zone Master Supplement

Data Aire, Inc.

230 W. BlueRidge Avenue

Orange, CA   92865

www.dataaire.com

Содержание dap4 touch

Страница 1: ...dap4 Zone Master Supplement Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...

Страница 2: ......

Страница 3: ...nd Addressing Units within a Zone 9 2 0 1 Wiring 9 2 0 2 Addressing unit within a Zone 9 2 0 3 Changing the address of the dap4 controller 10 2 0 3 1 Changing the address of the Mini dap4 controller 1...

Страница 4: ...on Temperature Control 1 1 Logic 1 1 1 Auto Lead Lag Standby Rotation and Temperature Assist Logic provides a means to au tomatically rotate the designation of STANDBY among a group of units that must...

Страница 5: ...messages will be displayed whenever a standby unit has been reactivated for operation If the temperature and humidity condition at the standby unit are satisfied it will return to inactive STBbyZM whe...

Страница 6: ...Off Day 4 ONbyZM ONbyZM STBbyZM Off Day 5 STBbyZM ONbyZM ONbyZM Off Day 6 ONbyZM STBbyZM ONbyZM Off Day 7 ONbyZM ONbyZM STBbyZM Off Note If communication with the Zone Master is broken all units will...

Страница 7: ...dependent of other zones Off alarm and standby alarm selection can not be duplicated The user may assign one or more alarms as OFF by selecting Y yes in Zone Master Alarms page see programming and sel...

Страница 8: ...prevented from continuing or starting humidifi cation NOTE An EXCLUDED message will display on the Zone Master when a unit is excluded from the zone by temperature or humidity calibration 1 2 Additio...

Страница 9: ...lded pair with a drain line Up to 16 units may be connected in any order daisy chained Unit addresses must be assigned at start up prior to wiring Each unit is connected through the unit s control mod...

Страница 10: ...Addresses needs to be done in order to establish a Zone Master communication Follow this procedure to set pLAN address to each dap4 controller in the zone Press button A for 5 seconds by using a small...

Страница 11: ...hich is display __ Use UP button to change I O board address to the address that is programmed in the steps above then press Enter Display will show Terminal config press ENTER to continue press Enter...

Страница 12: ...reach OK Yes No select Yes and press Enter to save the change and exit At this point the controller and the display should be communicating After addressing all individual units in a zone to the reco...

Страница 13: ...r Factory Password Press the Menu button The following screen will be displayed Press the Enter key The cursor will flash on the first 0 Enter a value by pressing either the Up or Down keys Once a val...

Страница 14: ...e units units 2 3 16 after they have been enabled and connected via pLAN with unit 1 master they will act as a member of the zone unless the user chooses otherwise To dis able a unit from the Zone Mas...

Страница 15: ...ne and cannot be changed It shows how many units are connected to the Zone Master via the pLan connection The master unit will automatically detect the online slave units Finish Run Stdby If yes is se...

Страница 16: ...ing in the title block Press the Down key The follow ing will be displayed entries are for reference only Temperature Assist Press the Enter key The cursor will flash by the current entry To change th...

Страница 17: ...the standby unit the Enter key is manu ally pressed If Day Time is selected an additional line for the day time will be displayed Press the Enter key once the Day Time selection has been made The cur...

Страница 18: ...in the title block press the Down key to see the next screen The follow ing message will be displayed entries are for reference only The unit may be set to either Stdby Standby or Off Press the Enter...

Страница 19: ...e the next screen The following message will be displayed entries are for reference only The alarm may be set to either yes or no Press the Enter key to move the cursor from one alarm to the next Pres...

Страница 20: ...ress the Down key to see the next screen The following message will be displayed entries are for reference only Press ESC key to get back to main menu 4 2 Programming Units with Primary Secondary Sche...

Страница 21: ...the cursor from unit to unit Press the Up or Down key to change from Stdby to Off Once selections have been made and with the cursor flashing in the title block press the Down key to see the next scre...

Страница 22: ...lock Repeat the same step for each day to be copied or select ALL Press the Enter key The cursor will flash on the No or Yes setting Pressing the Up or Down key will change from YES to NO or NO to YES...

Страница 23: ...ed month and day are the STOP DATE of the holiday Press the Enter key The cursor will flash on the SETTING input Press the Up or Down keys to scroll through the choices there are two PRIMARY and SECON...

Страница 24: ...been made and with the cursor flashing in the title block press the Down key to see the next screen The following message will be displayed entries are for reference only The alarm may be set to eithe...

Страница 25: ...ock press the Down key to see the next screen The following message will be displayed entries are for reference only The alarm may be set to either yes or off Press the Enter key to move the cursor fr...

Страница 26: ...__________________________________________________________________ __________________________________________________________________________ __________________________________________________________...

Страница 27: ......

Страница 28: ...dataaire com e mail sales dataaire com A Member of the CS Group of Companies 2012 Data Aire Inc Data Aire Inc reserves the right to make design changes for the purpose of product improvement or to wi...

Отзывы: