2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
464
List Manual, 09/2017, A5E33842890
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters
associated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motor: p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628
synchronous motor: p0326, p0327, p0352, p0604, p0605
Description:
Displays the commissioning steps that have been carried out.
Note:
The individual bits are only set if the appropriate action has been initiated and successfully completed.
The identification final display is reset when changing the type plate parameters.
Description:
Displays the base voltage for the alternating voltage in the context of motor data identification.
0:
No alternating voltages. The function is deactivated.
<0:
Automatic determination of the base voltage and wobbulation / self-setting based on the converter and the connected
motor.
Otherwise:
Base voltage for alternating current generation in volts (wobbulation active).
r3925[0...n]
Identification final display / Ident final_disp
Access level:
3
Calculated:
p0340 = 1
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Yes
No
-
02
Motor data identification carried out at
standstill (p1910 = 1)
Yes
No
-
03
Rotating measurement carried out (p1960 =
1, 2)
Yes
No
-
08
Identified motor data are automatically
backed up
Yes
No
-
11
Automatic parameterization as Standard
Drive Control
Yes
No
-
12
Automatic parameterization as Dynamic
Drive Control
Yes
No
-
14
First motor commissioning
Yes
No
-
15
Equivalent circuit diagram parameters
changed
Yes
No
-
16
Cable resistance measured
Yes
No
-
18
Circle identification executed
Yes
No
-
r3926[0...n]
Voltage generation alternating base voltage amplitude / U_gen altern base
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [V]
- [V]
- [V]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......