2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
476
List Manual, 09/2017, A5E33842890
Description:
Sets the phase for the LVDT sensor.
Description:
Sets the permissible tolerance in encoder pulses for the zero mark distance in the context of zero mark monitoring.
Causes fault F3x100 to appear less frequently.
Dependency:
Refer to: F31100
Description:
Sets the positive tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, then the pulse number is not corrected. If it is higher than this limit, fault F3x131
is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be deactivated using p0437.7.
Dependency:
Refer to: p0437, p4688
Refer to: F31131
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
The positive limit describes additional pulses due to EMC.
Description:
Sets the negative tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, the PPR is not corrected. If it is higher than this limit, fault F3x131 is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be deactivated using p0437.7.
Dependency:
Refer to: p0437, p4681, p4688
Refer to: F31131
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -1001, the negated value of p4681 is effective.
The negative limit describes the pulses lost due to a covered glass panel in the incremental encoder.
p4679[0...n]
Analog sensor LVDT phase / An_sens LVDT ph
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(4), T
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-360.00 [°]
360.00 [°]
0.00 [°]
p4680[0...n]
Zero mark monitoring tolerance permissible / ZM_monit tol perm
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1000
4
p4681[0...n]
Zero mark monitoring tolerance window limit 1 positive / ZM tol lim 1 pos
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1000
2
p4682[0...n]
Zero mark monitoring tolerance window limit 1 negative / ZM tol lim 1 neg
Access level:
3
Calculated:
-
Data type:
Integer32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-1001 0
-1001
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......