2 Parameters
2.2 List of parameters
Description:
Displays the function modules available on this drive device.
After setting p0010 = 11, additional function modules can be activated – or those that are not required, deactivated. A
change is only active after p0010 = 0.
For this drive device, only index 0 is relevant.
Dependency:
Active messages can prevent or influence activating a function module.
Refer to: p0010
Refer to: A07089, F13010
Note:
A "function module" is a functional expansion of a drive object that can be activated when commissioning.
Description:
Identification of the Control Unit using an LED.
Note:
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
Description:
Configuration of the motor when commissioning the motor.
p0108[0...n]
Function module 1 / Fct_module 1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0000 0000 0000 0000 0000
0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
02
Speed/torque control
Activated
Not activated
-
03
Position control
Activated
Not activated
-
04
Basic positioner
Activated
Not activated
-
08
Extended setpoint channel
Activated
Not activated
-
10
Moment of inertia estimator
Activated
Not activated
-
13
Safety rotary axis
Activated
Not activated
-
15
Encoder
Activated
Not activated
-
16
Technology controller
Activated
Not activated
-
17
Extended messages/monitoring
Activated
Not activated
-
18
Free function blocks
Activated
Not activated
-
23
Power Module 230 with STO
Activated
Not activated
-
25
Power Module 230
Activated
Not activated
-
26
F3E power unit
Activated
Not activated
-
27
DC braking
Activated
Not activated
-
28
Compound brake
Activated
Not activated
-
29
Dynamic brake
Activated
Not activated
-
30
Vdc_min controller
Activated
Not activated
-
31
Vdc_max controller
Activated
Not activated
-
p0124[0...n]
CU detection via LED / CU detection LED
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
U, T
Scaling:
-
Dyn. index:
PDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0
p0133[0...n]
Motor configuration / Motor config
Access level:
2
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor connection type
Delta
Star
-
01
Motor 87 Hz operation
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......