4 Faults and alarms
4.1 Overview of faults and alarms
SINAMICS G120 CU250S-2 Control Units
998
List Manual, 09/2017, A5E33842890
For the interfaces DP, ET 200, NAMUR, in some instances, the message classes are
combined.
Table 4-4
Message classes and coding of various diagnostic interfaces
Text of the message class (number according to PROFIdrive)
Cause and remedy.
Diagnostics interface
PN
(hex)
DS1
(dec)
DP
(dec)
ET 200
(dec)
NAMUR
(r3113.x)
Hardware/software errors (1)
A hardware or software malfunction was detected. Carry out a
POWER ON for the relevant component. If it occurs again, contact the
hotline.
9000
0
16
9
0
Line fault (2)
A line supply fault has occurred (phase failure, voltage level ...).
Check the line supply and fuses. Check the supply voltage. Check the
wiring.
9001
1
17
24
1
Supply voltage fault (3)
An electronics supply voltage fault (48 V, 24 V, 5 V …) was detected.
Check the wiring. Check the voltage level.
9002
2
2
1
3
2
2
3
15
DC-link overvoltage (4)
The DC-link voltage has assumed an inadmissibly high value. Check
the dimensioning of the system (line supply, reactor, voltages). Check
the infeed settings.
9003
3
18
24
2
Power electronics fault (5)
An impermissible operating state of the power electronics was
detected (overcurrent, overtemperature, IGBT failure …). Check
compliance with the permissible load cycles. Check the ambient
temperatures (fan).
9004
4
19
24
3
Overtemperature of the electronic component (6)
The temperature in the component has exceeded the highest
permissible limit. Check the ambient temperature / control cabinet
ventilation.
9005
5
20
5
4
Ground fault / inter-phase short-circuit detected (7)
A ground fault / inter-phase short-circuit was detected in the power
cables or in the motor windings. Check the power cables (connection).
Check the motor.
9006
6
21
20
5
Motor overload (8)
The motor was operated outside the permissible limits (temperature,
current, torque …). Check the load cycles and set limits. Check the
ambient temperature / motor cooling.
9007
7
22
24
6
Communication to the higher-level controller faulted (9)
The communication to the higher-level controller (internal coupling,
PROFIBUS, PROFINET …) is faulted or interrupted. Check the state
of the higher-level controller. Check the communication
connection/-wiring. Check the bus configuration/cycles.
9008
8
23
19
7
Safety monitoring channel has detected an error (10)
A safe operation monitoring function has detected an error.
9009
9
24
25
8
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......