2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
514
List Manual, 09/2017, A5E33842890
Description:
Sets the communication parameters for CANopen Receive Process Data Object 8 (RPDO 8).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1407 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1600 hex.
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1601 hex.
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
p8707[0...1]
CAN Receive PDO 8 / Receive PDO 8
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
p8710[0...3]
CAN Receive Mapping for RPDO 1 / Mapping RPDO 1
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204, 9206
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8711[0...3]
CAN Receive Mapping for RPDO 2 / Mapping RPDO 2
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204, 9206
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......