2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
140
List Manual, 09/2017, A5E33842890
Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description:
Sets the debounce time for digital inputs.
Note:
The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
Description:
Sets the bidirectional digital inputs/outputs as an input or output.
Note:
DI/DO: Bidirectional Digital Input/Output
Description:
Displays the access authority at the digital outputs.
Bit = 1:
The control has access authority to the digital output via PROFIBUS or direct access.
Bit = 0:
The drive has access authority to the digital output or the digital input/output is not set as digital output or is not
available.
Dependency:
Refer to: p0728, p0738, p0739, p0740, p0741, r0747, p0748
Note:
The DI/DO must be connected as output (p0728).
DI/DO: Bidirectional Digital Input/Output
p0724
CU digital inputs debounce time / CU DI t_debounce
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.000 [ms]
20.000 [ms]
4.000 [ms]
p0728
CU set input or output / CU DI or DO
Access level:
1
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2230, 2231
Min Max
Factory
setting
-
-
0000 0000 0000 0000 0000 0000 0000
0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
24
DI/DO 24 (T. 51)
Output
Input
-
25
DI/DO 25 (T. 52)
Output
Input
-
26
DI/DO 26 (T. 53)
Output
Input
-
27
DI/DO 27 (T. 54)
Output
Input
-
r0729
CU digital outputs access authority / CU DO acc_auth
Access level:
1
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2030, 2031
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (NO: T. 19 / NC: T. 18)
High
Low
-
01
DO 1 (NO: T. 21)
High
Low
-
02
DO 2 (NO: T. 24 / NC: T. 23)
High
Low
-
24
DI/DO 24 (T. 51)
High
Low
-
25
DI/DO 25 (T. 52)
High
Low
-
26
DI/DO 26 (T. 53)
High
Low
-
27
DI/DO 27 (T. 54)
High
Low
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......