2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
62
List Manual, 09/2017, A5E33842890
Description:
Selects the motor type or starts to read in the motor parameters for a motor with DRIVE-CLiQ (p0300 = 10000 or
10001, if there is a second data set).
For p0300 < 10000 the following applies:
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/AOP).
The following applies for values < 100:
Motor data must be manually entered.
The following applies for values >= 100:
Motor data are automatically loaded from an internal list.
Value:
0:
No motor
1:
Induction motor
2:
Synchronous motor
10:
1LE1 induction motor (not a code number)
13:
1LG6 induction motor (not a code number)
17:
1LA7 induction motor (not a code number)
19:
1LA9 induction motor (not a code number)
100:
1LE1 induction motor
101:
1PC1 induction motor
104:
1PH4 induction motor
105:
1LE5 induction motor
107:
1PH7 induction motor
108:
1PH8 induction motor
271:
1FG1 synchronous geared motor without encoder
277:
1FK7 synchronous motor without encoder
10000: Motor with DRIVE-CLiQ
10001: Motor with DRIVE-CLiQ 2nd data set
Dependency:
When selecting p0300 = 10 ... 19, parameters p0335, p0626, p0627, and p0628 of the thermal motor model are pre-
assigned as a function of p0307 and p0311.
Caution:
If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
Notice:
If a catalog motor is selected (p0300 >= 100) and an associated motor code number (p0301), then the parameters
that are associated with this list cannot be changed (write protection). The write protection is canceled if the motor
type p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 1 for p0301 = 1xxxx). Write protection is
automatically canceled when the results of motor data identification are copied to the motor parameters.
The motor type of a catalog motor corresponds to the upper three digits of the code number or the following
assignment (if the particular motor type is listed):
Type/code number ranges
100 / 100xx, 110xx, 120xx, 130xx, 140xx, 150xx
104 / 104xx, 114xx, 124xx
107 / 107xx, 117xx, 127xx,
108 / 108xx, 118xx, 128xx, 138xx, 148xx, 158xx
271 / 271xx, 281xx
277 / 277xx, 287xx, 297xx
p0300[0...n]
Motor type selection / Mot type sel
PM250
PM260
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS, p0130
Unit group:
-
Unit selection:
-
Func. diagram:
6310
Min Max
Factory
setting
0 10001
0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......