Description:
Displays the component of the fault which has occurred.
Value:
0:
No assignment
1:
Control Unit
2:
Power Module
3:
Motor
4:
Encoder evaluation (terminal)
5:
Encoder at term
6:
Encoder evaluation (SUB-D)
7:
Encoder at SUB-D
8:
Sensor Module (DRIVE-CLiQ)
9:
Encoder at Sensor Module
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
Description:
Displays the component of the alarm which has occurred.
Value:
0:
No assignment
1:
Control Unit
2:
Power Module
3:
Motor
4:
Encoder evaluation (terminal)
5:
Encoder at term
6:
Encoder evaluation (SUB-D)
7:
Encoder at SUB-D
8:
Sensor Module (DRIVE-CLiQ)
9:
Encoder at Sensor Module
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125, r2134, r2145, r2146, r3123
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description:
Displays the diagnostic attribute of the fault which has occurred.
r3120[0...63]
Component fault / Comp fault
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8060
Min Max
Factory
setting
0 9 -
r3121[0...63]
Component alarm / Comp alarm
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8065
Min Max
Factory
setting
0 9 -
r3122[0...63]
Diagnostic attribute fault / Diag_attr fault
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8060
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Hardware replacement recommended
Yes
No
-
15
Message has gone
Yes
No
-
16
PROFIdrive fault class bit 0
High
Low
-
17
PROFIdrive fault class bit 1
High
Low
-
18
PROFIdrive fault class bit 2
High
Low
-
19
PROFIdrive fault class bit 3
High
Low
-
20
PROFIdrive fault class bit 4
High
Low
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......