SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
169
2 Parameters
2.2 List of parameters
Note:
For bit 00:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switching on inhibited must be acknowledged via the source of p0840 =
0 (OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the main
contactor will open.
Description:
Sets the signal source to close the main contactor.
Note:
The main contactor is also closed when the converter is switched on after issuing the necessary enable signals. A
binector input p0870 = 1 signal prevents the main contactor from being opened when enable signals are withdrawn.
Description:
Sets the signal source to select the "parking axis" function.
Dependency:
BI: p0897 = 0 signal
The function "parking axis" is not selected.
BI: p0897 = 1 signal
The function "parking axis" is selected.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
After it has been selected the "parking axis" function only becomes active when the pulses are suppressed.
Description:
Display and connector output for the control word of the sequence control.
Note:
OC: Operating condition
p0870
BI: Close main contactor / Close main cont
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0
p0897
BI: Parking axis selection / Parking axis sel
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0
r0898.0...14
CO/BO: Control word sequence control / STW seq_ctrl
Access level:
2
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2501
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Enable operation
Yes
No
-
04
Enable ramp-function generator
Yes
No
-
05
Continue ramp-function generator
Yes
No
-
06
Enable speed setpoint
Yes
No
-
07
Command open brake
Yes
No
-
08
Jog 1
Yes
No
3001
09
Jog 2
Yes
No
3001
10
Master control by PLC
Yes
No
-
12
Speed controller enable
Yes
No
-
14
Command close brake
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......