Description:
Operating display for the drive.
Value:
0:
Operation - everything enabled
10:
Operation - set "enable setpoint" = "1" (p1142, p1152)
11:
Operation - set "enable speed controller" = "1" (p0856)
12:
Operation - RFG frozen, set "RFG start" = "1" (p1141)
13:
Operation - set "enable RFG" = "1" (p1140)
14:
Oper. - MotID, excit. running and/or brake opens, SS2, STOP C
15:
Operation - open brake (p1215)
16:
Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
17:
Operation - braking with OFF3 can only be interrupted with OFF2
18:
Operation - brake on fault, remove fault, acknowledge
19:
Operation - armature short-circ./DC brake act. (p1230, p1231)
21:
Ready for operation - set "Enable operation" = "1" (p0852)
22:
Ready for operation - de-magnetizing running (p0347)
23:
Ready for operation - set "Infeed operation" = "1" (p0864)
31:
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
35:
Switching-on inhibited - carry out first commissioning (p0010)
41:
Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
42:
Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
43:
Switching-on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
44:
Switching-on inhibited - supply STO terminal w/ 24 V (hardware)
45:
Switching-on inhibited - rectify fault, acknowledge fault, STO
46:
Switching-on inhibited - exit commissioning mode (p0009, p0010)
60:
Drive object de-activated/not operational
70:
Initialization
200:
Wait for booting/partial booting
250:
Device signals a topology error
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
STO: Safe Torque Off
Description:
Sets the access level to read and write parameters.
Value:
3:
Expert
4:
Service
r0002
Drive operating display / Drv op_display
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 250
-
p0003
Access level / Acc_level
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C, U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
3 4 3
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......