SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
521
2 Parameters
2.2 List of parameters
Description:
Sets the mapping parameters for CANopen Transmit Process Data Object 3 (TPDO 3).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1A02 hex.
The parameter can only be written online when the associated COB ID in p872x is set as invalid.
Description:
Sets the mapping parameters for CANopen Transmit Process Data Object 4 (TPDO 4).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1A03 hex.
The parameter can only be written online when the associated COB ID in p872x is set as invalid.
Description:
Sets the mapping parameters for CANopen Transmit Process Data Object 5 (TPDO 5).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1A04 hex.
The parameter can only be written online when the associated COB ID in p872x is set as invalid.
Description:
Sets the mapping parameters for CANopen Transmit Process Data Object 6 (TPDO 6).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
p8732[0...3]
CAN Transmit Mapping for TPDO 3 / Mapping TPDO 3
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9208, 9210
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8733[0...3]
CAN Transmit Mapping for TPDO 4 / Mapping TPDO 4
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9208, 9210
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8734[0...3]
CAN Transmit Mapping for TPDO 5 / Mapping TPDO 5
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9208
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8735[0...3]
CAN Transmit Mapping for TPDO 6 / Mapping TPDO 6
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9208
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......