2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
314
List Manual, 09/2017, A5E33842890
Description:
Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description:
Sets the reference quantity for acceleration rates.
All acceleration rates specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency:
This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting using
p0573 = 1.
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference acceleration is calculated as follows:
p2007 = p2000 / 1 [s]
Description:
Sets the baud rate for the commissioning interface (USS, RS232).
Value:
6:
9600 baud
7:
19200 baud
8:
38400 baud
9:
57600 baud
10:
76800 baud
11:
93750 baud
12:
115200 baud
Note:
COMM-IF: Commissioning interface
The parameter is not influenced by setting the factory setting.
Description:
Sets the address for the commissioning interface (USS, RS232).
Note:
The parameter is not influenced by setting the factory setting.
p2006
Reference temperature / Ref temp
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
-
Min Max
Factory
setting
50.00 [°C]
300.00 [°C]
100.00 [°C]
p2007
Reference acceleration / a_ref
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.01 [rev/s²]
500000.00 [rev/s²]
0.01 [rev/s²]
p2010
Comm IF baud rate / Comm baud
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
6 12
12
p2011
Comm IF address / Comm add
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 31
2
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......