SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
575
2 Parameters
2.2 List of parameters
Description:
Displays the necessary setpoint speed limit as a result of the selected motion monitoring functions.
Contrary to the parameterization of the SI limit values, this parameter specifies the motor-side limit value and not the
load-side limit value.
Recommendation:
For the ramp-function generator, by appropriately interconnecting the speed limits p1051 and p1052 with r9733[0, 1],
a drive-based setpoint velocity limiting can be realized.
- CI: p1051 = r9733[0]
- CI: p1052 = r9733[1]
Additional limiting can also be activated using connector input p1085 and p1088.
Index:
[0] = Setpoint limiting positive
[1] = Setpoint limiting negative
[2] = Setpoint limit absolute
Dependency:
For SLS: r9733[0] = p9531[x] x p9533 (converted from the load side to the motor side)
For SDI negative: r9733[0] = 0
For SLS: r9733[1] = - p9531[x] x p9533 (converted from the load side to the motor side)
For SDI positive: r9733[1] = 0
[x] = Selected SLS stage
Conversion factor from the motor side to the load side:
- motor type = rotary and axis type = linear: p9522 / (p9521 x p9520)
- otherwise: p9522 / p9521
Refer to: p9531, p9533
Notice:
If p1051 = r9733[0] is interconnected, p1052 = r9733[1] must also be interconnected and vice versa.
If only the absolute value of the setpoint velocity limiting is required, r9733[2] must be interconnected.
Note:
If the "SLS" function is not selected, r9733[0] shows p1082 and r9733[1] shows -p1082.
The display in r9733 can be delayed by up to one Safety monitoring clock cycle as compared to the display in r9720
and r9722.
Description:
Display and BICO output for status word S_ZSW1B of the safety information channel.
Note:
SIC: Safety Info Channel
For bit 07:
An internal event is displayed if a STOP A ... F is active.
r9733[0...2]
CO: SI Motion setpoint speed limit effective / SI Mtn setp_lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
2820, 2824, 3630
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r9734.0...14
CO/BO: SI Safety Info Channel status word S_ZSW1B / SIC S_ZSW1B
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
STO active
Yes
No
-
01
SS1 active
Yes
No
-
04
SLS active
Yes
No
-
06
SLS selected
Yes
No
-
07
Internal event
Yes
No
-
09
Select SLS bit0
Yes
No
-
10
Select SLS bit1
Yes
No
-
12
SDI positive selected
Yes
No
-
13
SDI negative selected
Yes
No
-
14
ESR retract requested
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......