2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
28
List Manual, 09/2017, A5E33842890
Description:
Displays the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
Dependency:
Refer to: r0021, r0063
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
Description:
Displays the smoothed output frequency.
Frequency components from the slip compensation (for induction motors) are included.
Dependency:
Refer to: r0066
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
Description:
Displays the smoothed output voltage of the power unit.
Dependency:
Refer to: r0072
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
Description:
Displays the smoothed actual value of the DC link voltage.
Dependency:
Refer to: r0070
Notice:
When measuring a DC link voltage < 200 V, for the Power Module a valid measured value is not supplied. In this
case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
r0022
Actual speed rpm smoothed / Actual speed
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6799
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0024
Output frequency smoothed / Output frequency
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 6799
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r0025
CO: Output voltage smoothed / U_outp smooth
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
5730, 6300, 6799
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r0026
CO: DC link voltage smoothed / Vdc smooth
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6799
Min Max
Factory
setting
- [V]
- [V]
- [V]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......