2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
324
List Manual, 09/2017, A5E33842890
Description:
Diagnostics display for the PROFIBUS interface.
Index:
[0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
Description:
Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency:
Refer to: p0918
Notice:
The display is updated after switching on, and not cyclically.
Description:
Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
Dependency:
Refer to: r2050
Notice:
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Description:
Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
r2055[0...2]
PROFIBUS diagnostics standard / PB diag standard
CU250S_V_DP
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
- - -
r2057
PROFIBUS address switch diagnostics / PB addr_sw diag
CU250S_V_DP
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
- - -
r2060[0...10]
CO: PROFIdrive PZD receive double word / PZD recv DW
Access level:
3
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2440, 2468
Min Max
Factory
setting
- - -
p2061[0...15]
CI: PROFIBUS PZD send double word / PZD send DW
Access level:
3
Calculated:
-
Data type:
U32 / Integer32
Can be changed:
U, T
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2470
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......