2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
186
List Manual, 09/2017, A5E33842890
Description:
Display and connector output for the selected and active fixed speed setpoint.
This setpoint is the output value for the fixed speed setpoints and must be appropriately interconnected (e.g. with the
main setpoint).
Recommendation:
Interconnect the signal with the main setpoint (CI: p1070 = r1024).
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1070, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
Description:
Display and binector output for the status when selecting the fixed speed setpoints.
Dependency:
Refer to: p1016
Note:
For bit 00:
When the fixed speed setpoints are directly selected (p1016 = 1), this bit is set if at least 1 fixed speed setpoint is
selected.
Description:
Sets the configuration for the motorized potentiometer.
Notice:
The following prerequisites must be fulfilled in order to be able to save the setpoint (Bit 03 = 1) in a non-volatile
fashion:
- Firmware with V2.3 or higher.
- Control Unit 320 (CU320) with hardware version C or higher (module with NVRAM).
Note:
For bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p1040.
1: The setpoint for the motorized potentiometer is saved after OFF and after ON set to the saved value. In order to
save in a non-volatile fashion, bit 03 should be set to 1.
r1024
CO: Fixed speed setpoint effective / Speed fixed setp
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3001, 3010, 3011
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r1025.0
BO: Fixed speed setpoint status / n_setp_fix status
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed speed setpoint selected
Yes
No
3011
p1030[0...n]
Motorized potentiometer configuration / Mop configuration
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
-
-
0000 0110 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Data save active
Yes
No
-
01
Automatic mode ramp-function generator
active
Yes
No
-
02
Initial rounding-off active
Yes
No
-
03
Save in NVRAM active
Yes
No
-
04
Ramp-function generator always active
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......