SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
1091
4 Faults and alarms
4.2 List of faults and alarms
A07466
EPOS: Traversing block number assigned a multiple number of times
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The same traversing block number was assigned a multiple number of times.
Alarm value (r2124, interpret decimal):
Number of the traversing block that was assigned a multiple number of times.
Remedy:
Correct the traversing blocks.
A07467
EPOS: Traversing block has illegal task parameters
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The task parameter in the traversing block contains an illegal value.
Alarm value (r2124, interpret decimal):
Number of the traversing block with an illegal task parameter.
Remedy:
Correct the task parameter in the traversing block.
A07468
EPOS: Traversing block jump destination does not exist
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
In a traversing block, a jump was programmed to a non-existent block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with a jump destination that does not exist.
Remedy:
- correct the traversing block.
- add the missing traversing block.
A07469
EPOS: Traversing block < target position < software limit switch minus
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the traversing block the specified absolute target position lies outside the range limited by the software limit switch
minus.
Alarm value (r2124, interpret decimal):
Number of the traversing block with illegal target position.
Remedy:
- correct the traversing block.
- change software limit switch minus (CI: p2578, p2580).
A07470
EPOS: Traversing block> target position > software limit switch plus
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the traversing block the specified absolute target position lies outside the range limited by the software limit switch
plus.
Alarm value (r2124, interpret decimal):
Number of the traversing block with illegal target position.
Remedy:
- correct the traversing block.
- change software limit switch plus (CI: p2579, p2581).
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......