2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
158
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, r0836
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description:
Sets the signal source to select the Command Data Set bit 1 (CDS bit 1).
Dependency:
Refer to: r0050, p0810, r0836
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description:
Copies one Drive Data Set (DDS) into another.
Index:
[0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Dependency:
Refer to: r3996
Notice:
When the drive data sets are copied, short-term communication interruptions may occur.
Note:
Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In index 1, enter the drive data set data that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description:
Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
CU250S_V
CU250S_V_CAN
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8560
Min Max
Factory
setting
- - 0
p0811
BI: Command data set selection CDS bit 1 / CDS select., bit 1
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8560
Min Max
Factory
setting
- - 0
p0819[0...2]
Copy Drive Data Set DDS / Copy DDS
Access level:
2
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(15)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8565
Min Max
Factory
setting
0 3 0
p0820[0...n]
BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
C(15), T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
8565, 8575
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......