SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
371
2 Parameters
2.2 List of parameters
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2247
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
Description:
Sets the mode for using the technology controller output.
Value:
0:
Technology controller as main speed setpoint
1:
Technology controller as supplementary speed setpoint
Dependency:
p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
Description:
Sets the configuration of the technology controller.
p2248[0...n]
Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
7954
Min Max
Factory
setting
0.0 [s]
1000.0 [s]
10.0 [s]
r2250
CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7954
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2251
Technology controller mode / Tec_ctrl mode
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0 1 0
p2252
Technology controller configuration / Tec_ctrl config
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
p0340 = 1
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
04
Ramp-up/ramp-down function generator
bypass
Deactivated
Activated
-
05
Integrator active for skip speeds
Yes
No
-
06
Internal controller limit not displayed
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......