4 Faults and alarms
4.2 List of faults and alarms
A07489
EPOS: Reference point correction outside the window
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the function "flying referencing" the difference between the measured position at the measuring probe and the
reference point coordinate lies outside the parameterized window.
Remedy:
- check the mechanical system.
- check the parameterization of the window (p2602).
F07490 (N)
EPOS: Enable signal withdrawn while traversing
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
- for a standard assignment, another fault may have occurred as a result of withdrawing the enable signals.
- the drive is in the "switching-on inhibited" state (for a standard assignment).
Remedy:
- set the enable signals or check the cause of the fault that first occurred and then result (for a standard assignment).
- check the assignment to enable the basic positioning function.
F07491 (A)
EPOS: STOP cam minus reached
Message class:
Application/technological function faulted (17)
Reaction:
OFF3
Acknowledge:
IMMEDIATELY
Cause:
A 0 signal was detected at binector input BI: p2569, i.e. the STOP cam minus was reached.
For a positive traversing direction, the STOP cam minus was reached - i.e. the wiring of the STOP cam is incorrect.
See also: p2569 (EPOS STOP cam minus)
Remedy:
- leave the STOP cam minus in the positive traversing direction and return the axis to the valid traversing range.
- check the wiring of the STOP cam.
F07492 (A)
EPOS: STOP cam plus reached
Message class:
Application/technological function faulted (17)
Reaction:
OFF3
Acknowledge:
IMMEDIATELY
Cause:
A 0 signal was detected at binector input BI: p2570, i.e. the STOP cam plus was reached.
For a negative traversing direction, the STOP cam plus was reached - i.e. the wiring of the STOP cam is incorrect.
See also: p2570 (EPOS STOP cam plus)
Remedy:
- leave the STOP cam plus in the negative traversing direction and return the axis to the valid traversing range.
- check the wiring of the STOP cam.
F07493
LR: Overflow of the value range for position actual value
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The value range (-2147483648 ... 2147483647) for the position actual value representation was exceeded.
When the overflow occurs, the "referenced" or "adjustment absolute measuring system" status is reset.
Fault value (r0949, interpret decimal):
1: The position actual value (r2521) has exceeded the value range.
2: The encoder position actual value Gn_XIST2 (r0483) or the absolute value after the load gear (r2723) has
exceeded the value range.
3: The maximum encoder value times the factor to convert the absolute position (r0483 and/or r2723) from
increments to length units (LU) has exceeded the value range for displaying the position actual value.
Note:
For a linear encoder, the following must be maintained:
- p0407 * p2503 / (2^p0418*10^7) < 1
- p0407 * p2503 / (2^p0419*10^7) < 1
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......