2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
126
List Manual, 09/2017, A5E33842890
38:
ft³/min
39:
BTU/min
40:
BTU/h
41:
mbar
42:
inch wg
43:
ft wg
44:
m wg
45:
% r.h.
46:
g/kg
47:
ppm
Dependency:
Only the unit of the technology controller parameters are switched over (unit group 9_1).
Refer to: p0596
Note:
When switching over from % into another unit, the following sequence applies:
- set p0596
- set p0595 to the required unit
Description:
Sets the reference quantity for the technological units.
When changing over using changeover parameter p0595 to absolute units, all of the parameters involved refer to the
reference quantity.
Dependency:
Refer to: p0595
Notice:
When changing over from one technological unit into another, or when changing the reference parameter, a
changeover is not made.
Description:
Sets the sensor to monitor the motor temperature.
The sensor type used is set in p0601.
Value:
0:
No sensor
1:
Temperature sensor via encoder 1
11:
Temperature sensor via Motor Module / CU terminals
12:
Temperature sensor via CU-D-SUB
Dependency:
Refer to: p0601
Caution:
If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another sensor,
then the temperature adaptation of the motor resistances must be switched out. Otherwise, in controlled-loop
operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice:
The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
Note:
For p0600 = 0:
With induction motors, the motor temperature is calculated using the motor temperature model (see also p0612.1).
For p0600 = 1:
Bimetallic switch (p0601 = 4) is not supported.
p0596
Technological unit reference quantity / Tech unit ref qty
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.01 340.28235E36
1.00
p0600[0...n]
Motor temperature sensor for monitoring / Mot temp_sensor
Access level:
2
Calculated:
p0340 = 1
Data type:
Integer16
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
8016
Min Max
Factory
setting
0 12
11
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......