SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
567
2 Parameters
2.2 List of parameters
Description:
Sets the PROFIsafe address for processor 1.
Dependency:
Refer to: p9810
Description:
Sets the discrepancy time for the changeover of the fail-safe digital input for STO on processor 1.
An F-DI changeover is not effective simultaneously due to the different runtimes in the two monitoring channels. After
an F-DI changeover, dynamic data is not subject to a data cross-check during this discrepancy time.
Dependency:
Refer to: p9850
Note:
For a data cross-check between p9650 and p9850, a difference of one Safety monitoring clock cycle is tolerated.
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
F-DI: Fail-safe Digital Input
Description:
Sets the debounce time for the fail-safe digital input used to control STO/SBC/SS1.
The debounce time is rounded to whole milliseconds.
Note:
The debounce time is rounded to whole milliseconds. It specifies the maximum duration of a fault pulse at the fail-
safe digital inputs with no reaction/influence on the selection or deselection of the Safety Basic Functions.
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
Description:
Sets the delay time of the pulse suppression for the "Safe Stop 1" (SS1) function on processor 1 to brake along the
OFF3 down ramp (p1135).
Recommendation:
In order that the drive can completely ramp-down along the OFF3 ramp and a motor holding brake that is possibly
available can close, then the delay time should be set as follows:
Motor holding brake parameterized: delay time >= p1135 + p1228 + p1217
Motor holding brake not parameterized: delay time >= p1135 + p1228
Dependency:
Refer to: p1135, p9852
Note:
For a data cross-check between p9652 and p9852, a difference of one Safety monitoring clock cycle is tolerated.
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
p9610
SI PROFIsafe address (processor 1) / SI PROFIsafe P1
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0000 hex
FFFE hex
0000 hex
p9650
SI F-DI changeover discrepancy time (processor 1) / SI F-DI chg t P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2810
Min Max
Factory
setting
0.00 [ms]
2000.00 [ms]
500.00 [ms]
p9651
SI STO/SBC/SS1 debounce time (processor 1) / SI STO t_debou P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
1.00 [ms]
p9652
SI Safe Stop 1 delay time (processor 1) / SI Stop 1 t_del P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [s]
300.00 [s]
0.00 [s]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......