SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
235
2 Parameters
2.2 List of parameters
Description:
Defines the voltage boost as a [%] referred to the rated motor current (p0305).
The magnitude of the permanent voltage boost is reduced with increasing frequency so that at the rated motor
frequency, the rated motor voltage is present.
The magnitude of the boost in Volt at a frequency of zero is defined as follows:
Voltage boost [V] = 1.732 x p0305 (rated motor current [A]) x r0395 (stator/primary section resistance [ohm]) x p1310
(permanent voltage boost [%]) / 100 %
At low output frequencies, there is only a low output voltage in order to maintain the motor flux. However, the output
voltage can be too low in order to achieve the following:
- magnetize the induction motor.
- hold the load.
- compensate for losses in the system.
This is the reason that the output voltage can be increased using p1310.
The voltage boost can be used for both linear as well as square-law U/f characteristics.
For field orientation (p1302.4 = 1, default setting for Standard Drive Control p0096 = 1), in the vicinity of low output
frequencies, a minimum current is impressed with the magnitude of the rated magnetizing current. In this case, for
p1310 = 0%, a current setpoint is calculated that corresponds to the no-load case. For p1610 = 100 %, a current
setpoint is calculated that corresponds to the rated motor current.
Dependency:
The starting current (voltage boost) is limited by the current limit p0640.
Only for p1302.4 = 0 (no field orientation):
The accuracy of the starting current depends on the setting of the stator and feeder cable resistance (p0350, p0352).
For vector control, the starting current is realized using p1610.
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1300, p1311, p1312, r1315
Notice:
The starting current (voltage boost) increases the motor temperature (particularly at zero speed).
Note:
The starting current as a result of the voltage boost is only effective for U/f control (p1300).
The boost values are combined with one another if the permanent voltage boost (p1310) is used in conjunction with
other boost parameters (acceleration boost (p1311), voltage boost for starting (p1312)).
However, these parameters are assigned the following priorities: p1310 > p1311, p1312
For field orientation (p1302 bit 4 = 1, not PM230, PM250, PM260), then p1310 together with p1311 and p1302.5 are
mainly responsible for the quality of the drive response.
Description:
Defines the voltage boost as a [%] referred to the rated motor current (p0305).
The magnitude of the permanent voltage boost is reduced with increasing frequency so that at the rated motor
frequency, the rated motor voltage is present.
The magnitude of the boost in Volt at a frequency of zero is defined as follows:
Voltage boost [V] = 1.732 x p0305 (rated motor current [A]) x r0395 (stator/primary section resistance [ohm]) x p1310
(permanent voltage boost [%]) / 100 %
p1310[0...n]
Starting current (voltage boost) permanent / I_start (Ua) perm
PM240
Access level:
2
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 6301, 6851
Min Max
Factory
setting
0.0 [%]
250.0 [%]
50.0 [%]
p1310[0...n]
Starting current (voltage boost) permanent / I_start (Ua) perm
PM250
PM260
Access level:
2
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 6301
Min Max
Factory
setting
0.0 [%]
250.0 [%]
50.0 [%]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......