SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
489
2 Parameters
2.2 List of parameters
Description:
Sets the phase shift of the second system with respect to the first system for the motor module for a 12-pulse gating
unit.
Value:
0:
Shift by +30 °
1:
Shift by -30 °
2:
Shift by 0 °
3:
Shift by +90 °
4:
Shift by -90 °
5:
Shift by +120 °
6:
Shift by -120 °
7:
Shift by +150 °
8:
Shift by -150 °
Notice:
The parameter is only evaluated if p7003 = 2.
Note:
For p6397 = 0 the following applies: The second systems leads for a positive direction of rotation.
For p6397 = 1 the following applies: The second systems lags for a positive direction of rotation.
Description:
Displays the actual serial number of the Control Unit.
The individual characters of the serial number are displayed in the ASCII code in the indices.
For the commissioning software, the ASCII characters are displayed uncoded.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Notice:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Note:
KHP: Know-How Protection
Description:
Sets the reference serial number for the Control Unit.
Using this parameter, if a Control Unit and/or a memory card is replaced at the end customer, the OEM can again
adapt the project to the modified hardware.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
- the OEM may only change this parameter for the use case "Sending encrypted SINAMICS data".
- SINAMICS only evaluates this parameter when powering up from the encrypted "Load into file system..." output or
when powering up from the encrypted PS files. The evaluation is only made when know-how protection and memory
card copy protection have been activated.
p6397
Motor module phase shift second system / MM ph_sh 2nd sys
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 8 0
r7758[0...19]
KHP Control Unit serial number / KHP CU ser_no
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p7759[0...19]
KHP Control Unit reference serial number / KHP CU ref ser_no
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......