manualshive.com logo in svg
background image

R180

AVR

Installation and maintenance

Содержание Leroy-Somer R180

Страница 1: ...R180 AVR Installation and maintenance...

Страница 2: ...arning symbol for electrical danger to personnel All servicing or repair operations perfor med on theAVR should be undertaken by personnel trained in the commissioning servicing and maintenance of ele...

Страница 3: ...nge 7 4 2 Connection diagram for high voltage range with droop powered by AREP 8 4 3 Connection diagram for high voltage range with droop powered by PMG 9 5 AVR SETTINGS 10 6 TROUBLESHOOTING CHART 11...

Страница 4: ...and 5 A signal from a droop current transformer in U phase to give a voltage droop which allows the alternator to operate in parallel The R180 has an accessory input which can be used as a remote pote...

Страница 5: ...xiliary input and external potentio meter range The auxiliary input range is set by the potentiometer marked Acc This potentiometer sets the maximum voltage range for the external potentiometer or the...

Страница 6: ...y 10 s 350 V peak 5 Up to 75 Hz 8 Excitation current 6 A DC continuous 9 A for 5 seconds short circuit operation 9 Regulation 1 at AVR sensing terminals 10 Maximum excitation limit 6 A DC factory sett...

Страница 7: ...7 Electric Power Generation 2019 10 e Installation and maintenance R180 AVR 5599 en 4 MAIN FUNCTION OF THE AVR 4 1 Connection diagram for low voltage range 0V...

Страница 8: ...8 Electric Power Generation 2019 10 e Installation and maintenance R180 AVR 5599 en 4 2 Connection diagram for high voltage range with droop powered by AREP 0V...

Страница 9: ...9 Electric Power Generation 2019 10 e Installation and maintenance R180 AVR 5599 en 4 3 Connection diagram for high voltage range with droop powered by PMG 0V...

Страница 10: ...t the terminals using the voltage adjustment potentiometer If oscillations are seen on the voltmeter A C indicating the alternator terminal voltage gradually turn the STABILITY trimmer on the R180 clo...

Страница 11: ...rnal potentiometer link open Connect link or potentiometer as necessary Loss of sensing voltage Connect as per the diagram Prime mover rpm falls Set rpm Incorrect regulation Prime mover rpm falls Set...

Страница 12: ...lead to X2 The multimeter will display 0 4 V to 0 6 V Connect the red lead to Z1 The multimeter will display 0 4 V to 0 6 V Connect the red lead to Z2 The multimeter will display 0 4 V to 0 6 V Connec...

Страница 13: ...potentiometer 250 V 110 V transformer 8 2 Connection Connect the 100 W bulb between the F1 and F2 terminals on the AVR Connect the 110 V transformer output to X1 and X2 on the AVR Connect the 250 V en...

Страница 14: ...tage to 400 VAC The bulb will up light because the setpoint is 415 V Now turn on the switch which is connected to the 50 Hz 60 Hz input The bulb will gradually go OFF due to the change in the UFRO set...

Страница 15: ...15 Electric Power Generation 2019 10 e 147 115 90 56 5 11 16 117 159 142 Installation and maintenance R180 AVR 5599 en 9 DIMENSIONS TOP VIEW SIDE VIEW...

Страница 16: ...ion you may require For all spare parts orders or technical support requests send your request to service epg leroy somer com or your nearest contact whom you will find at www lrsm co support indicati...

Страница 17: ...ith local legislation regarding product disposal and recycling Waste hazardous materials The following components and materials require special treatment and must be separated from the alternator befo...

Страница 18: ...18 Electric Power Generation 2019 10 e Installation and maintenance R180 AVR 5599 en...

Страница 19: ...ient repair support and maintenance services Trust your alternator maintenance and support to electric power generation experts Our field personnel are 100 qualified and fully trained to operate in al...

Страница 20: ...www emersonindustrial com 2019 10 e www leroy somer com epg 5599 en Linkedin com company leroy somer Twitter com Leroy_Somer_en Facebook com LeroySomer Nidec en YouTube com LeroySomerOfficiel...

Отзывы: