SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
601
2 Parameters
2.2 List of parameters
Note:
If value = 0:
No terminal assigned, safety function always selected.
If value = 255:
No terminal assigned, safety function always deselected.
F-DI: Fail-safe Digital Input
SDI: Safe Direction (safe motion direction)
Description:
Selects the individual signals that should be logically combined to create "Safe State"
Description:
Sets the signal sources for F-DO 0 (X131.5).
The 6 signal sources in p10042[0...5] are AND'ed and the result is output at F-DO 0.
Value:
0:
No function
1:
STO active
2:
SS1 active
5:
SLS active
6:
SSM feedback signal active
7:
Safe state
9:
Internal event
12:
SDI positive active
13:
SDI negative active
Index:
[0] = AND logic operation input 1
[1] = AND logic operation input 2
[2] = AND logic operation input 3
[3] = AND logic operation input 4
[4] = AND logic operation input 5
[5] = AND logic operation input 6
Note:
F-DO: Fail-safe Digital Output
Description:
Activates the readback input for the safety digital output (F-DO)
The test mode for the particular safety digital output is set in p10047.
p10039
SI Motion Safe State signal selection (processor 1) / SI Safe State P1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2856
Min Max
Factory
setting
-
-
0000 0001 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Power_removed
Selected
Not selected
-
01
SS1_active
Selected
Not selected
-
04
SLS_active
Selected
Not selected
-
05
SDI_pos_active
Selected
Not selected
-
06
SDI_neg_active
Selected
Not selected
-
p10042[0...5]
SI Motion F-DO signal sources (processor 1) / SI Mtn F-DOs_srcP1
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2877
Min Max
Factory
setting
0 13
0
p10046
SI Motion F-DO feedback signal input activation / SI F-DO FS act
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Test F-DO 0
Test active
No test
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......