SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
353
2 Parameters
2.2 List of parameters
Description:
Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2164, p2166, r2197
Description:
Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off"
signal/message (BO: r2197.7).
Dependency:
Refer to: p2163, p2166, r2197
Description:
Sets the switch-off delay time for the "speed setpoint - actual value deviation in tolerance t_off" signal/message (BO:
r2197.7).
Dependency:
Refer to: p2163, p2164, r2197
Description:
Sets the switch-on delay for the "speed setpoint - actual value deviation in tolerance t_on" signal/message (BO:
r2199.4).
Description:
Display and connector output of the smoothed speed actual value for messages.
Dependency:
Refer to: p2153
p2163[0...n]
Speed threshold 4 / n_thresh val 4
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8011
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
90.00 [rpm]
p2164[0...n]
Hysteresis speed 4 / n_hysteresis 4
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8011
Min Max
Factory
setting
0.00 [rpm]
200.00 [rpm]
2.00 [rpm]
p2166[0...n]
Off delay n_act = n_set / t_del_off n_i=n_so
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8011
Min Max
Factory
setting
0.0 [ms]
10000.0 [ms]
200.0 [ms]
p2167[0...n]
Switch-on delay n_act = n_set / t_on n_act=n_set
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8011
Min Max
Factory
setting
0.0 [ms]
10000.0 [ms]
200.0 [ms]
r2169
CO: Actual speed smoothed signals / n_act smth message
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8010
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......