SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
555
2 Parameters
2.2 List of parameters
Description:
Sets the enable signals for the safe motion monitoring.
Dependency:
Refer to: F01682, F01683
Note:
A change only becomes effective after a POWER ON.
For bit 30 = 1, PROFIsafe telegram 900 must be configured in the F host.
SDI: Safe Direction (safe motion direction)
SLS: Safely Limited Speed
SSM: Safe Speed Monitor (safety-relevant feedback signal from the speed monitoring)
Description:
Sets the enable signals for the safe motion monitoring.
Dependency:
Refer to: F01682, F01683
Note:
A change only becomes effective after a POWER ON.
For bit 30 = 1, PROFIsafe telegram 900 must be configured in the F host.
SDI: Safe Direction (safe motion direction)
SLS: Safely Limited Speed
SSM: Safe Speed Monitor (safety-relevant feedback signal from the speed monitoring)
Description:
Sets the function specification for the safe motion monitoring.
Value:
1:
Safety without encoder with brake ramp (SBR)
3:
Safety without encoder with accel_monitoring (SAM) / delay time
Dependency:
Refer to: C01711
p9501
SI Motion enable safety functions (processor 1) / SI Mtn enable P1
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0000 0000 0000 0000 0000
0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable SI Motion
Enable
Inhibit
-
16
Enable SSM hysteresis and filtering
Enable
Inhibit
2823
17
Enable SDI
Enable
Inhibit
2824
30
Enable F-DI in PROFIsafe telegram
Enable
Inhibit
-
p9501
SI Motion enable safety functions (processor 1) / SI Mtn enable P1
CU250S_V
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0000 0000 0000 0000 0000
0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable SI Motion
Enable
Inhibit
-
16
Enable SSM hysteresis and filtering
Enable
Inhibit
2823
17
Enable SDI
Enable
Inhibit
2824
p9506
SI Motion function specification (processor 1) / SI Mtn fct_spc P1
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
1 3 1
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......