2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
504
List Manual, 09/2017, A5E33842890
Note:
For a value = 9999999, the following applies: The read operation is still running.
Description:
Displays the ACX file saved in the appropriate directory in the non-volatile memory.
Dependency:
Refer to: p1500
Note:
For a value = 9999999, the following applies: The read operation is still running.
Description:
Displays the macro currently being executed on the drive object.
Dependency:
Refer to: p0015, p1000, p1500, r8570, r8571, r8572, r8573
Description:
Displays all of the devices connected to the CAN bus after run-up.
r8600
= 00000000 hex: No drive recognized.
= 02010192 hex: 1 vector drive.
Note:
Corresponds to the CANopen object 1000 hex.
For each detected drive, the device type is displayed in object 67FF hex.
Description:
Displays the error register for CANopen.
Bit 0: Generic error.
0 signal: No error present.
1 signal: Generic error present.
Bit 1 ... 3: Not supported (always a 0 signal).
Bit 4: Communications error.
0 signal: There is no message in the range 8700 ... 8799.
1 signal: There is at least one message (fault or alarm) in the range 8700 ... 8799.
Bit 5 ... 6: Not supported (always a 0 signal).
Bit 7: Fault outside the range 8700 ... 8799.
0 signal: There is no fault outside the range 8700 ... 8799.
1 signal: There is at least one fault outside the range 8700 ... 8799.
Note:
Corresponds to the CANopen object 1001 hex.
r8573[0...39]
Macro Connector Inputs (CI) for torque setpoints / Macro CI M_set
Access level:
4
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r8585
Macro execution actual / Macro executed
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r8600
CAN device type / Device type
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r8601
CAN error register / Error register
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......