SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
35
2 Parameters
2.2 List of parameters
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a "switching-on inhibited".
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 02 = 1 (enable signal missing), if:
- the signal source in p0848 or p0849 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
- the signal source in p0852 is a 0 signal.
Bit 04 =1 (armature short-circuit active), if:
- the signal source in p1230 has a 1 signal.
Bit 05, Bit 06: Being prepared
Bit 08 = 1 (enable signal missing), if:
- safety functions have been enabled and STO is active.
- STO is selected via onboard terminals or PROFIsafe.
- a safety-relevant signal is present with STOP A response.
- the "STO via terminals at the Power Module" function is selected.
Bit 09 = 1 (enable signal missing), if:
- the signal source in p0864 is a 0 signal.
Bit 10 = 1 (enable signal missing), if:
- the signal source in p1140 is a 0 signal.
Bit 11 = 1 (enable signal missing) if the speed setpoint is frozen, because:
- the signal source in p1141 is a 0 signal.
- the speed setpoint is entered from jogging and the two signal sources for jogging, bit 0 (p1055) and bit 1 (p1056)
have a 1 signal.
Bit 12 = 1 (enable signal missing), if:
- the signal source in p1142 is a 0 signal.
- When activating the function module "basic positioner" (r0108.4 = 1), the signal source in p1142 is set to a 0 signal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enabled if the fault is removed and was acknowledged and the
"switching-on inhibited" withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- commissioning mode is selected (p0010 > 0).
- there is an OFF2 fault response.
- the drive is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
08
Safety enable missing
Yes
No
-
09
Infeed enable missing
Yes
No
-
10
Ramp-function generator enable missing
Yes
No
-
11
Ramp-function generator start missing
Yes
No
-
12
Setpoint enable missing
Yes
No
-
15
QuickStop enable missing
Yes
No
-
16
OFF1 enable internal missing
Yes
No
-
17
OFF2 enable internal missing
Yes
No
-
18
OFF3 enable internal missing
Yes
No
-
19
Pulse enable internal missing
Yes
No
-
20
Armature short-circuit/DC braking internal
enable missing
Yes
No
-
21
STOP2 enable internal missing
Yes
No
-
25
Function bypass active
Yes
No
-
26
Drive inactive or not operational
Yes
No
-
27
De-magnetizing not completed
Yes
No
-
28
Brake open missing
Yes
No
-
29
Cooling unit ready signal missing
Yes
No
-
30
Speed controller inhibited
Yes
No
-
31
Jog setpoint active
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......