2 Parameters
2.2 List of parameters
Description:
Sets the ramp-down time for the ramp-function generator.
The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill
(setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency:
Refer to: p1082, p1123
Note:
For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
Description:
Sets the signal source for bypassing the ramp generator (ramp-up and ramp-down times = 0).
Caution:
If the technology controller is operated in mode p2251 = 0 (technology controller as main speed setpoint), then it is
not permissible to disable the interconnection to its status word (r2349).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
In the case of sensorless vector control, the ramp-function generator must not be bypassed, other than indirectly by
means of interconnection with r2349.
Description:
Sets the minimum ramp-up time.
The ramp-up time (p1120) is limited internally to this minimum value.
Dependency:
Refer to: p1082
Note:
The setting should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1123 is re-calculated.
Description:
Sets the minimum ramp-down time.
The ramp-down time (p1121) is limited internally to this minimum value.
The parameter cannot be set shorter than the minimum ramp-up time (p1123).
Dependency:
Refer to: p1082
p1121[0...n]
Ramp-function generator ramp-down time / RFG ramp-down time
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(1), U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3060, 3070
Min Max
Factory
setting
0.000 [s]
999999.000 [s]
10.000 [s]
p1122[0...n]
BI: Bypass ramp-function generator / Bypass RFG
Access level:
4
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2505
Min Max
Factory
setting
- - 0
p1123[0...n]
Ramp-function generator minimum ramp-up time / RFG t_RU min
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.000 [s]
999999.000 [s]
0.000 [s]
p1127[0...n]
Ramp-function generator minimum ramp-down time / RFG t_RD min
PM240
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.000 [s]
999999.000 [s]
0.000 [s]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......