SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
599
2 Parameters
2.2 List of parameters
Dependency:
Refer to: p10001, p10002, p10003, p10046
Description:
Sets the debounce time for digital inputs.
The debounce time is accepted rounded off to whole milliseconds.
The debounce time acts on the following digital inputs:
- Fail-safe digital inputs (F-DI).
- Single-channel digital inputs (DI).
- Single-channel digital input 5 (DI 5, read back input for the forced checking procedure).
Dependency:
Refer to: p10117
Note:
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
The debounce result can be read in r10051.
Description:
Sets the fail-safe digital input (F-DI) for the "STO" function.
Value:
0:
Static selected
1:
F-DI 0
2:
F-DI 1
3:
F-DI 2
255:
Static deselected
Dependency:
Refer to: p10122
Note:
If value = 0:
No terminal assigned, safety function always selected.
If value = 255:
No terminal assigned, safety function always deselected.
F-DI: Fail-safe Digital Input
STO: Safe Torque Off
Description:
Sets the fail-safe digital input (F-DI) for the "SS1" function.
Value:
0:
Static selected
1:
F-DI 0
2:
F-DI 1
3:
F-DI 2
255:
Static deselected
Dependency:
Refer to: p10123
Note:
If value = 0:
No terminal assigned, safety function always selected.
p10017
SI Motion digital inputs debounce time (processor 1) / SI DI t_debounceP1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
1.00 [ms]
p10022
SI Motion STO input terminal (processor 1) / SI Mtn STO F-DI P1
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 255
0
p10023
SI Motion SS1 input terminal (processor 1) / SI Mtn SS1 F-DI P1
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 255
0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......