2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
142
List Manual, 09/2017, A5E33842890
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Description:
Sets the signal source for terminal DO 2 (NO: T. 24 / NC: T. 23).
Recommendation:
r0052.0 Ready for switching on
r0052.1 Ready for operation
r0052.2 Operation enabled
r0052.3 Fault present
r0052.4 Coast down active (OFF2)
r0052.5 Quick stop active (OFF3)
r0052.6 Switching-on inhibited active
r0052.7 Alarm present
r0052.9 Control request
r0052.14 Motor rotates forwards
r0053.0 DC braking active
r0053.1 n_act > p2167 (n_off)
r0053.2 n_act <= p1080 (n_min)
r0053.3 I_act > p2170
r0053.4 n_act > p2155
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Description:
Sets the signal source for terminal DI/DO 24.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.24 = 1).
DI/DO: Bidirectional Digital Input/Output
p0732
BI: CU signal source for terminal DO 2 / CU S_src DO 2
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2119, 2030, 2130
Min Max
Factory
setting
- - 52.2
p0738
BI: CU signal source for terminal DI/DO 24 / CU S_src DI/DO 24
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2201, 2230
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......